High Voltage Polymer Arrester (YH10W-36kv)
- Description
- Reviews (0)
Description
Standards: IEC 60099-4
The ambient air themperatures is no higher than +40° C, no lower than-40° C.
The altitude above sea level dose not exceed 2000m.
AC system frequency is 50Hz or 60Hz.
AC voltage brought to bear on arrester for a long time dose not exceed arrester’s
continuous operating voltage.
Maximum wind speed dose not exceed 35m/s.
The earthquake intensity dose not exceed 7 degrees.
Type |
Rated Voltage | Maximun
Continuous Operating Voltage |
Current impulse residual voltage |
2ms Rectangular
current impulse withstand |
4/10µ s High current impulse withstand |
||
1/4µ s
Lightning Current impulse |
8/20µ s
Lightning current impulse |
30/60µ s
Switching current impulse |
|||||
kV(rms) | kV(rms) | kV(crest) | kV(crest) | kV(crest) | (A) | kA(crest) | |
YH10W- 36 | 36 | 29.0 | 123 | 108 | 92.4 | 250 |
100 |
Reviews